ups电源故障指示灯详细解说
工作状态 |
面板灯号显示 |
故障编号 |
||||||||||
1# |
2# |
3# |
4# |
5# |
6# |
7# |
8# |
9# |
10# |
|||
市电工作模式 |
0%~35%负载量 |
|
|
|
|
|
● |
|
● |
● |
|
|
36%~55%负载量 |
|
|
|
|
● |
● |
|
● |
● |
|
|
|
56%~75%负载量 |
|
|
|
● |
● |
● |
|
● |
● |
|
|
|
76%~95%负载量 |
|
|
● |
● |
● |
● |
|
● |
● |
|
|
|
96%~105%负载量 |
|
● |
● |
● |
● |
● |
|
● |
● |
|
|
|
电池工作模式/电池检测模式 |
0%~25%电池容量 |
|
● |
|
|
|
|
|
|
● |
● |
|
26%~50%电池容量 |
|
● |
● |
|
|
|
|
|
● |
● |
|
|
51%~75%电池容量 |
|
● |
● |
● |
|
|
|
|
● |
● |
|
|
76%~100%电池容量 |
|
● |
● |
● |
● |
|
|
|
● |
● |
|
|
100%电池容量 |
|
● |
● |
● |
● |
● |
|
|
● |
● |
|
|
旁路工作模式 |
0%~35%负载量 |
|
|
|
|
|
● |
● |
● |
|
|
|
36%~55%负载量 |
|
|
|
|
● |
● |
● |
● |
|
|
|
|
56%~75%负载量 |
|
|
|
● |
● |
● |
● |
● |
|
|
|
|
76%~95%负载量 |
|
|
● |
● |
● |
● |
● |
● |
|
|
|
|
96%~105%负载量 |
|
● |
● |
● |
● |
● |
● |
● |
|
|
|
|
过载 |
市电模式过载,未转旁路输出(告警中) |
|
● |
● |
● |
● |
● |
|
● |
● |
|
22 |
市电模式过载,输旁路输出(保护动作) |
|
● |
● |
● |
● |
● |
● |
● |
|
|
||
市电模式过载,转旁路输出时间到,关闭输出.(保护动作). |
● |
● |
|
|
|
|
|
↑ |
|
|
||
电池模式过载,预警中 |
|
● |
↑ |
↑ |
↑ |
↑ |
|
|
● |
● |
||
电池模式过载,关断输出(保护动作) |
● |
● |
|
|
|
|
|
↑ |
|
|
||
温度侦测异常 |
过温 |
● |
|
|
|
|
● |
↑ |
↑ |
|
|
23 |
NTC温度检测异常 |
● |
|
|
|
|
● |
↑ |
↑ |
|
|
55 |
|
BUS电压异常 |
● |
|
|
● |
|
|
↑ |
↑ |
|
|
1, 2, 3 |
|
充电器输出电压过高(过充) |
● |
|
● |
|
|
|
↑ |
↑ |
|
|
cWC1L_OverChg |
|
输出短路 |
● |
● |
|
|
● |
|
↑ |
↑ |
|
↑ |
10 |
|
负功故障 |
● |
● |
● |
● |
|
|
↑ |
↑ |
|
|
17 |
|
不均流故障 |
● |
|
● |
● |
|
● |
↑ |
↑ |
|
|
21 |
|
|
市电Fuse故障 |
● |
|
● |
|
● |
|
↑ |
↑ |
|
|
42 |
ID重复 |
● |
● |
|
● |
|
|
↑ |
|
|
|
54 |
|
工作电源异常Fault |
● |
● |
|
● |
● |
● |
↑ |
↑ |
↑ |
↑ |
36 |
|
逆变异常 |
● |
|
|
|
● |
|
↑ |
↑ |
|
|
6, 7, 8 |
|
逆变RLY粘死 |
● |
|
|
● |
|
● |
↑ |
↑ |
|
|
25 |
|
逆变RLY断开 |
● |
|
|
|
● |
● |
↑ |
↑ |
|
|
24 |
|
PFC故障 |
● |
|
|
● |
● |
|
↑ |
↑ |
|
|
5, 24, 29 |
|
市电SCR故障 |
● |
|
|
● |
● |
● |
↑ |
↑ |
|
|
26 |
|
并机通信故障 |
● |
● |
● |
|
|
● |
↑ |
↑ |
|
|
59\60\61 |
|
UPS机种类型非法 |
● |
|
● |
● |
● |
● |
↑ |
↑ |
|
|
100 |
|
附板故障 |
● |
● |
|
● |
|
● |
↑ |
↑ |
↑ |
↑ |
cWC1H_SlaveBoardFail |
|
缺相告警(3相输入的系统) |
● |
● |
● |
|
|
|
↑ |
↑ |
↑ |
↑ |
cWC1L_LineLoss |
|
读取参数错误 |
● |
● |
|
● |
● |
|
↑ |
↑ |
↑ |
↑ |
cWC3L_EepromFail |
|
电池OPEN(电池丢失) |
↑ |
↑ |
↑ |
↑ |
↑ |
● |
|
|
|
★ |
cWC1L_BatOpen |
|
充电板或电池损坏 |
● |
|
|
|
|
|
|
|
|
★ |
cWC1H_ChgFail |
|
风扇工作异常 |
● |
● |
|
|
|
● |
↑ |
↑ |
↑ |
|
cWC1L_FanLock |
|
电池电压低 |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
★ |
cWC1L_BatLow |
|
市电输入零火线接反 |
|
↑ |
↑ |
↑ |
↑ |
● |
↑ |
★ |
↑ |
↑ |
cWC1L_SiteFail |
|
电池故障 |
● |
|
● |
● |
|
|
↑ |
↑ |
|
|
57 |
|
EPO状态(EPO模式) |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
★ |
★ |
★ |
★ |
cWC1L_EpoActive |
|
converter模式 |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
|
↑ |
★ |
↑ |
|
|
不满足开机条件 |
● |
|
● |
|
|
● |
↑ |
↑ |
↑ |
↑ |
cWC1H_TurnOnAbornaml |
|
ECO模式 |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
★ |
● |
|
|
|
|
电池自检测模式 |
↑ |
↑ |
↑ |
↑ |
↑ |
↑ |
7 9 10 8灯一个接一个亮和灭,一直循环显示(如7先亮,接着灭,然后就是9灯亮和灭……) |
|
||||
LED检测 |
LED显示状态 |
首先1`6灯全亮,接着6灭,再就是5灭,4,3,2,1一个接一个灭 |
|
|||||||||
条件: 关机或开机时,电池自检模式. |
|
YITENSANTE ups电源
指示灯所标识故障有不明白的致电我公司:4000859896 01052452696